l Optimal Use For:

| Name | Automatic Voltage Stabilizer PDR Series (3-Phase Servo Type) | ||||
| Model | PT3-10KVA | PT3-15KVA | PT3-20KVA | PT3-30KVA | |
| Rated Power | 10000VA/6000W | 15000VA/9000W | 20000VA/12000W | 30000VA/18000W | |
| Technology | Three Phase AVR + Independent Phase Control + Digital CPU Control | ||||
| Transformer | Servo Motor Type (Mix Copper and Aluminum) | ||||
| Input | Nominal Voltage | 260-430Vac | |||
| Frequency | 50/60Hz | ||||
| Output | Voltage | 380Vac, ±3% | |||
| Respond Time | <1s, against 10% variation of input voltage | ||||
| Efficiency | >98% | ||||
| Protection | High Voltage | Output Cutoff by Contactor + Show "H" on Display + Buzzer Beeping | |||
| Low Voltage | Output Cutoff by Contactor + Show "L" on Display + Buzzer Beeping | ||||
| Overheat | Output Cutoff by Contactor + Show "CH" on Display + Buzzer Beeping | ||||
| Overload | Output Cutoff by Contactor + Show "OL" on Display + Buzzer Beeping | ||||
| Phase Failure | Output Cutoff by Contactor + Show "L" on Display + Buzzer Beeping | ||||
| Short Circuit | Input Cutoff by Air Breaker | ||||
| Output Delay | 6s/180s selectable | ||||
| Safety Standard | Insulation Voltage | 2000V/60S | |||
| Insulation Resistance | >5mΩ | ||||
| Cooling | Smart Fan (Automatic Startup at 65°C) | ||||
| Certification | CE (LVD + EMC) | ||||
| Operating Environment | Temperature | —5°C~+50°C | |||
| Humidity | 10%~90% Non-Condensing | ||||
| Unit Weight / N.W. | 45.0 kgs | 50.0 kgs | 69.0 kgs | 82.0 kgs | |
| Giftbox Size (mm) | 435*395*850 | 435*395*850 | 505*455*830 | 505*455*830 | |
| Carton Size (Wooden Pallet mm) | 490*450*880 | 490*450*880 | 555*505*880 | 555*505*880 | |